In Quebec, installations continue throughout the winter, it is simply part of the job. However, cold weather changes the rules. A slow evacuation, an incorrect refrigerant charge or a compressor started while cold can lead to callbacks when temperatures reach −20°C. Follow these cold-weather heat pump installation best practices to ensure a proper commissioning, even in the middle of winter.
1. Evacuation: The Most Critical Step in Winter
This is where cold temperatures have the greatest impact. At low temperatures, residual moisture inside the system evaporates much more slowly, and may even freeze, making it considerably more difficult to achieve a deep vacuum than during summer.
-
Always evacuate the system to below 500 microns using a micron gauge, followed by a decay test.
-
Allow more time than you would during warmer weather. Achieving a deep vacuum takes longer in extreme cold.
-
Warm the components when possible, as heat helps the remaining moisture evaporate.
-
Use short, large-diameter hoses and a properly maintained vacuum pump with clean oil.
Cutting corners during a winter evacuation can leave moisture trapped inside the system. That moisture may freeze at the expansion device and damage the compressor.
2. Charge by Weight, Not by Pressure
In cold weather, the unit cannot reliably be operated in cooling mode to adjust the charge based on pressure. The conventional charging method therefore becomes unreliable.
-
Use the weigh-in method: the manufacturer’s factory charge plus the required adjustment based on the actual line-set length.
-
Measure the refrigerant accurately using a reliable scale.
-
Document the amount of refrigerant added for future service and warranty records.
This is the most accurate method when outdoor temperatures prevent reliable pressure-based verification.
3. Crankcase Heater and Low-Temperature Start-Up
In extreme cold, refrigerant migrates toward the coldest part of the system, often the compressor crankcase. Starting a compressor containing liquid refrigerant can cause liquid slugging and oil dilution.
-
Energize the unit in advance so the crankcase heater has enough time to operate before the initial start-up. Follow the manufacturer’s recommended waiting period.
-
Confirm that the compressor is not flooded with liquid refrigerant before starting the cycle.
-
Monitor the pressures and system operation carefully during low-temperature start-up.
4. Handling Frozen Piping and Materials
Cold temperatures make copper tubing rigid and other materials brittle, creating an often-overlooked source of installation errors.
-
Keep the tubing and insulation warm before bending or flaring. A flare made on frozen copper may crack.
-
Tighten flare connections to the manufacturer’s recommended torque.
-
Braze while flowing nitrogen to prevent internal oxidation, and allow for the additional heat required in cold conditions.
-
Handle plastic drains and conduits carefully, as they become brittle in extreme cold.
A2L reminder: When working with the all-R32 product lineup, continue following A2L refrigerant handling practices—including proper ventilation, an A2L-compatible leak detector and the elimination of ignition sources near an open refrigerant circuit, even during winter.
5. Protect the Condensate Drain from Freezing
In heating mode, the outdoor unit produces condensate, particularly during defrost cycles, and this water can freeze quickly.
-
Maintain a continuous slope and unobstructed drainage path.
-
Provide freeze protection for exposed drains through appropriate routing or supplemental heat when required.
-
Elevate the outdoor unit on an appropriate stand or raised mounting rack above the expected snow level.
6. Commissioning: Confirm Heating and Defrost Operation
Before leaving the job site, verify that the entire system operates correctly under actual winter conditions.
-
Test the reversing valve operation and heating mode.
-
Confirm proper operation of the defrost cycle.
-
Check the pressures and system performance at the current outdoor temperature.
-
Document the commissioning process, including the refrigerant charge, readings and completed tests.
FAQ
Why Does Evacuation Take Longer in Winter?
At low temperatures, residual moisture evaporates more slowly and may freeze. Additional time, a micron gauge and a decay test are required to confirm that a deep vacuum has been achieved.
How Should a Heat Pump Be Charged in Cold Weather?
Use the weigh-in method: start with the manufacturer’s factory charge and adjust it according to the actual line-set length. Pressure-based verification in cooling mode is not reliable during cold weather.
Why Should You Wait Before Starting the Compressor?
The waiting period allows the crankcase heater to remove liquid refrigerant that has migrated into the compressor crankcase, reducing the risk of liquid slugging during start-up.